Online High Frequency UPS From Three-three phase 10KVA-40KVA 60KVA-80KVA

1. Large input voltage range: full load: 275Vac-475Vac; no-load:210Vac-475Vac

2. Large input frequency range: The UPS can work in mains INV mode if the input ranges from 40 to 70Hz.

3. High output accuracy: ±1% output voltage error.

PRODUCT FEATURES:

  • 1. High-frequency online three-in and three-out UPS, the output can be connected to unbalanced load, and the input three-phase always keeps the load balanced.
  • 2. Fully digital control,more stable performance.
  • 3. Energy-saved and environmental protection, efficiency is up to 93%
  • 4. Support N+X parallel redundancy
  • 5. The most optimized tower structure design has the smallest volume compared to similar products on the market
  • 6. A single set of battery supplies power to the system, reducing the number of batteries and save cost.
  • 7. 10-20K standard machine integrated design with battery built-in, easy to install and use.
  • 8. Visualized LCD display interface, clear and intuitive display of three-phase working information.
  • 9. Intelligent mobile monitoring cards are supported to monitor UPS data in real time through mobile apps.

 

Description:

PARAMETER XT33 60-80KVA

PARAMETER  XT33 10-40KVA

 

Model XT33 10KVA XT33 10KS XT33 20KVA XT33 20KS XT33 30KS XT33 40KS
Rated Power 10kVA/9kW 20kVA/18kW 30kVA/27kW 40kVA/36kW
Input Voltage Range 207-475Vac 3P4W+G
Working Frequency Range 40-70Hz (settable)
Input Power Factor ≥0.95
Output Rated Voltage and Accuracy 380Vac(1±1%) 3P4W+G
Output Frequency 46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz ); 50Hz(Battery)
Rated Current 15A 30A 45A 61A
Output Power Factor 0.9
Output Harmonic Wave ≤3%
Crest Factor 3: 1
Output Overload 105%±5%<Load≤125%±5%: Convert to bypass output and alarm after 1min;
125%±5%<Load≤150%±5%: Convert to bypass output and alarm after 30s;
Load>150%±5%: Convert to bypass output and alarm after 300ms.
Conversion time between Mains Power and Battery 0ms
Efficiency >92% >91%
Battery Rated Voltage 192Vdc ±192Vdc
Quantity 16 32
Charging Current 1A 5.5A 1A 7.5A 5.5A
Dimension (LxWxH) mm 560x260x717 533x260x501 710x260x717 710x260x717
Weight 72kg 26kg 98kg 57.5kg 58.5kg 62kg
Working Temperature 0℃-40℃
Working  Humidity 20%-95%
Noise ≤60dB